ADCA Sample Coolers SC32P – SC32PP

Product Benefits

  • Corrosion-resistant body and internals.
  • Self-draining sample (top inlet, bottom outlet).
  • SC32P – permanent sampling.
  • SC32PP – portable design.
  • Multiple connections available
  • Simple design
  • Internal wetted parts: ≤ 0.51 micron Ra – SF1
  • External surface: ≤0.76 microns Ra – SF3
  • Ultrasonic cleaning

Technical Data

  • Max. Pressure: Body: 20 Barg / Coil: SC32P: 110 Barg / SC32PP 90 Barg
  • Max. Temp: Body: 120°C / Coil: SC32P: 400°C / SC32PP 450°C
  • Size & Connections: Cooling water inlet/outlet: ½” on body (BSP or NPT) or ¾” tri-clamp. Sample tube inlet/outlet: 8 mm O/D. Alternative ½” tri-clamp compatible

Material:

  • Body: 1.4404 (316L)
  • Cover: 1.4404 (316L)
  • Coil: 1.4404 (316L)
  • Compression fittings: AISI 316Ti / 1.4571 Cl. L
  • Discharge tube: 1.4404 (316L)
  • Finishes: Interior surfaces SF1 / External surfaces SF3
  • Certificates: EN10204 3.1 certificate and internal coil surface finish certification available if requested with the order.
  • Packaging: Assembled and packed in a clean room certified according to ISO 14644-1. This product is end-capped and sealed with recyclable thermo-shrinkable plastic film, to avoid contamination.
  • Installation: Vertical installation.
  • Operation: Cooling water must be at its maximum flow before opening or closing the sample inlet valve, to avoid scalding. The sample valve must also be closed before opening the cooling water valve. The sample coil should always be completely immersed in water.
  • Performance: 30 to 60 kg/h of sample water at ≈ 30 ºC with 1 m3 /h – 15 ºC inlet Cooling water (boilers up to 20 bar – 220 ºC). For other pressures, temperatures and/or certified figures please consult ESI.

Application

To obtain a sample of water which has been saturated from Steam Condensate from steam headers, steam subheaders, upstream at control stations and expansion loops, heating coils, condensing equipment, boilers, steam tracing manifolds, and steam tracing lines. This is for the main purpose of testing the quality of steam/condensate.

Make An Enquiry

    Information provided on this form will be used for sales follow up and for marketing purposes. You can opt out at any time. Click here to read our privacy policy for full details.
  • This field is for validation purposes and should be left unchanged.

Let's Connect!

Get in touch with our dedicated team. We are here to help!